Technical Guide to Current Transformer (CT) Accuracy, Risk Assessment, and Laboratory Testing

 

Agenda:

  1. Key Factors Influencing Current Transformer Accuracy
  2. Accuracy Verification of Metering-Class Current Transformers
  3. Saturation Control and Performance Verification of Protection-Class CTs
  4. Technical Risks Associated with Insufficient CT Verification
  5. Role of Certified Laboratories and Verification Capability


Why CT Accuracy Verification Matters in Practical Systems?

In power metering and protection systems, Current Transformers (CTs) serve as the interface between high primary currents and measurable secondary signals. Their accuracy and stability directly affect billing precision and the correct operation of protection relays under fault conditions.

CTs that have not been verified by laboratories compliant with IEC 61869-2 or UL requirements may exhibit ratio error and phase displacement deviations under real operating conditions. While such deviations may be negligible during normal operation, they can become critical under low-load, high-load, or fault-current scenarios.

For this reason, CT performance evaluation should not rely solely on nominal ratings. Systematic laboratory verification is essential to confirm compliance under actual application conditions.

Key Factors Influencing Current Transformer Accuracy

Core Material and Magnetic Characteristics

CT accuracy is strongly influenced by core material selection. Silicon steel, nanocrystalline alloys, and other high-permeability materials differ in magnetic permeability, saturation flux density, and loss characteristics. These properties affect excitation current magnitude, saturation behavior, and stability during transient or high-current conditions.

Winding Structure and Burden Dependency

Winding configuration, turn ratio, and conductor impedance directly affect CT linearity and ratio accuracy under different secondary burden conditions. Even CTs with identical nominal ratings may exhibit different error behavior when operating with varying burdens, making burden-dependent verification essential.

Accuracy Verification of Metering-Class Current Transformers

Applicable Accuracy Classes and Operating Range

Metering CTs are required to maintain stable accuracy over a wide current range. Laboratory verification typically covers operating currents from 1% to 120% of rated current to ensure reliable performance at both low-load and near-rated conditions.

  • Accuracy classes: 0.2S, 0.5S, 1.0, 3.0.

Laboratory Verification Focus

Verification focuses on:

  • Ratio error and phase displacement under different burdens
  • Linearity across the specified operating range
  • Prevention of cumulative measurement errors during long-term operation

These evaluations ensure predictable accuracy under practical metering conditions.

Saturation Control and Performance Verification of Protection-Class CTs

Protection Accuracy Classes and Accuracy Limit Factor (ALF)

Protection CTs are designed to remain reliable under high fault currents. A key performance criterion is whether the composite error remains within the specified Accuracy Limit Factor (ALF).

  • Accuracy classes: 5P10, 10P20, 10P5, and 10P10.

Excitation Characteristics and Knee Point Evaluation

Excitation (V–I curve) testing is used to determine the knee point voltage, which indicates the margin before core saturation occurs. This information is critical for assessing CT behavior during short-circuit fault conditions.

System-Level Engineering Impact

If a CT enters saturation prematurely during a fault, the resulting distortion of secondary current waveforms may cause differential or overcurrent protection relays to operate incorrectly or with delay, increasing overall system risk.

Technical Risks Associated with Insufficient CT Verification

1. Core Saturation Leading to Protection Failure

Protection CTs with insufficient design margin or without ALF verification may saturate under high-multiple short-circuit currents. Saturation distorts the secondary current, preventing protection relays from accurately sensing primary conditions.

2. Accuracy Drift Due to Thermal Effects

During long-term operation, temperature variation and harmonic content can influence excitation current. Unverified CTs may experience ratio error drift of approximately 0.5%–2.0% as excitation losses increase with temperature, affecting metering accuracy.

3. Secondary Open-Circuit Overvoltage

The secondary circuit of a CT must never be left open. If an open circuit occurs, the primary current is converted entirely into excitation current, driving the core into severe saturation and generating kilovolt-level induced voltages:

                       

Such voltages can cause insulation breakdown and pose safety hazards to equipment and personnel.

Role of Certified Laboratories and Verification Capability

Certified laboratories employ high-accuracy reference CTs, digital CT calibrators, burden boxes, standard power sources, and resistance measurement equipment to systematically verify:

  • Ratio accuracy and phase displacement
  • Excitation characteristics and ALF
  • Accuracy retention under varying burden conditions
  • Winding resistance, polarity, and design consistency
Equipment NameFunction
HS-30G2 Precision Current TransformerServes as a reference standard, providing high-accuracy current (0.02 class error) for measuring ratio error and phase displacement of the CT under test.
HES-1Cx Digital CT CalibratorPerforms comprehensive testing of CT excitation characteristics, ratio, polarity, and secondary resistance, automatically calculating 10% error curves and Accuracy Limit Factor (ALF).
FY49 CT Burden BoxSimulates secondary loads (2.5–60 VA) to verify CT accuracy retention under varying burdens, with automatic switching between test points.
STR1060A Single-Phase Standard Power SourceProvides stable test current and voltage (0.05% accuracy) for ratio and error measurements.
ZX21 DC Decade Resistance BoxPrecisely measures secondary winding resistance with 0.001 Ω resolution, ensuring proper insulation and contact.
AWE2101C-UR Power MeterMeasures power, current, and voltage, verifying energy conversion efficiency and linearity.
8808A MultimeterProvides auxiliary measurement of power, current, and voltage, confirming accuracy and reliability of results.
YG-108 Air-Core Coil Turn TesterChecks the number of turns in primary and secondary windings to validate CT ratio design.

 

By leveraging this combination of equipment, the laboratory can comprehensively verify CT ratio accuracy, phase displacement, load performance, and design consistency, providing repeatable and reliable measurements for downstream metering and protection systems.

 

Current Transformers play a central role in both metering and protection systems. Their accuracy and reliability directly influence operational safety and billing precision. By understanding CT performance parameters, associated technical risks, and the role of certified laboratory verification, engineers and design decision-makers can make more informed and robust design choices, ensuring dependable long-term power system operation.